HY Serie - Hanyoung - Controles de Temperatura Análogo (HY-4500 / HY-5000)
- Fabricante: Hanyoung Nux
- Código de Producto: HY Serie Análogo
- Existencia: Disponible
Control de Temperatura Análogo HY Serie (HY-4500)
Características principales:
- Control proporcional o ON/OFF
- Simple selección de temperatura
- Ajuste por perilla (corrección, comprobación e intercambio simple)
Suffix code
[ HY-4500S / HY-5000 ] |
Model | Suffix Code | Information | |||||
HY- | Analog indication temperature controller | ||||||
Dimension | 4500S | 96(W) × 96(H) | |||||
5000 | 72(W) × 72(H) | ||||||
Adjusting action | F | ON/OFF control (2 position control) | |||||
P | Proportional control | ||||||
Input | K | K thermocouple | |||||
J | J thermocouple | ||||||
R | R thermocouple | ||||||
D | Resistance Temperature Detector(RTD) KPt100 Ω | ||||||
P | Resistance Temperature Detector(RTD) Pt100 Ω(IEC) | ||||||
V | 1 - 5 V d.c | ||||||
C | 4 - 20 mA d.c | ||||||
Control Output | M | Relay Output | |||||
C | Current output (4 - 20 mA d.c) | ||||||
S | S.S.R (12 V d.c Voltage pulse output) | ||||||
Control operation | R | Reverse action (Heating control) | |||||
D | Direct action (Cooling control) | ||||||
Range code | Select the standard range code |
[ HY-4500S / HY-5000 ] |
Model / Code No. | HY-4500S | HY-5000 | ||
Input | Temp. Range | Input | Temp. Range | |
1 | Pt100 Ω | -50 ~ 50 | Pt100 Ω | -50 ~ 50 |
3 | Pt100 Ω | -50 ~ 100 | Pt100 Ω | 0 ~ 100 |
5 | Pt100 Ω | 0 ~ 100 | K, Pt100 Ω | 0 ~ 200 |
6 | - | - | K, Pt100 Ω | 0 ~ 300 |
7 | K, Pt100 Ω | 0 ~ 200 | K, Pt100 Ω | 0 ~ 400 |
8 | K, Pt100 Ω | 0 ~ 300 | K | 0 ~ 600 |
9 | K, J, Pt100 Ω | 0 ~ 400 | K | 0 ~ 800 |
10 | K | 0 ~ 600 | K | 0 ~ 1200 |
11 | K | 0 ~ 800 | - | - |
13 | K | 0 ~ 1200 | - | - |
14 | R | 0 ~ 1600 | - | - |
Specification
[ HY-4500S / HY-5000 ] |
Model | HY-4500S | HY-5000 | |||
Appearance | |||||
Power supply voltage | 110 V a.c / 220 V a.c, 60 Hz | ||||
Allowable voltage fluctuation | ±10 % of power supply voltage | ||||
Power consumption | Approx. Max 3 VA | ||||
Input | Thermocouple, Resistive, d.c Current, d.c Voltage (see Standard Range Code)(Built - in Burnout circuit) | ||||
Adjusting Sensitivity | ±0.2%(fixed) of Max. Range | ||||
Control Method | Proportional Control, ON / OFF Control | ||||
Setting Method | Analog Setting | ||||
Display Method | Analog Display | ||||
Control Output |
| ||||
Setting Accuracy | 2 % of Max. Range | ||||
Display Accuracy | ±2.0 % of F.S ±1 digit | ||||
Proportional Band | 1 ~ 10 % of Max. Range(variable) | 3 % of Max. Range(fixed) | |||
Proportional Cycle | Relay Output : 20 ~ 30 sec / SSR Output : 2 ~ 4 sec | ||||
Insulation Resistance | 20 ㏁ min ( 500 V a.c mega) | ||||
Dielectric Strength | 2000 V a.c 50 ~ 60 Hz for 1 minute | ||||
Noise Immunity | Squared wave noise(pulse width : 1000 µs) ±1 KV | ||||
Vibration Resistance | 10 - 50 Hz (cycle for 1 minute), double amplitude : 0.75 mm, each X Y Z direction for 1 hour | ||||
Shock Resistance | 300 ㎨ | ||||
Relay Life Expectancy | Mechanical : 10 millions times, Electrical : 100 thousands times (250 V a.c, 3 A Resistive Load) | ||||
Ambient Temperature/Humidity | 0 ~ 50 °C / 35 ~ 85 % R.H (without condensation) | ||||
Weight | 658 g (Including brackets) | 358 g (Including brackets) |