KX Serie - Hanyoung - Controles de Temperatura Digital
- Fabricante: Hanyoung Nux
- Código de Producto: KX Serie
- Existencia: Disponible
Control de Temperatura Digital KX Serie
Características principales:
- Entradas universales
- Selección de la posición del punto decimal
- Operación de salida: selección de funcionamiento directo o inverso
- Sintonización automatica PID
- Alarma de ruptura de resistencia
- 2 alarmas (alta y baja)
![]() | ![]() |
Suffix code
| Model | Code | Information | |||||
| KX | Digital Temperatrue Contoller | ||||||
| Dimension | 2N | 48(W) × 96(H) mm | |||||
| 3N | 96(W) × 48(H) mm | ||||||
| 4N | 48(W) × 48(H) mm | ||||||
| 7N | 72(W) × 72(H) mm | ||||||
| 9N | 96(W) × 96(H) mm | ||||||
| 4S | 48(W) × 48(H) mm | for 11 pin socket | |||||
| Control output | M | Relay | |||||
| S | SSR (Voltage pulse 12 V DC) | ||||||
| C | SCR (Current 4 - 20 mA DC) | ||||||
| Alarm output | C | * KX4N, KX4S selection only | ALH, ALL, LBA (1a common output) | ||||
| E | * KX4S selection inhibited | ||||||
| KX2N, KX3N, KX9N | ALH(1c), ALL(1a) | ||||||
| KX7N, KX4N (option) | ALH(1a), ALL(1a) | ||||||
| K | * KX4N, KX4S selection inhibited | ||||||
| KX2N, KX3N, KX9N (optional) | ALH(1c), ALL(1a), LBA(1a) | ||||||
| KX7N (optional) | ALH(1a), ALL(1a), LBA(1a) | ||||||
| Retransmission output (Option) | A | * Only selectable with models given in the below KX4N-□C KX2N-□E, KX3N-□E, KX9N-□E KX2N-□K, KX3N-□K, KX9N-□K | Retransmission output(RET) 4 - 20 mA d.c | ||||
| N | None | ||||||
| Power Supply Voltage | A | 100 - 240 V a.c, 50 - 60 Hz | |||||
| D | 24 V d.c (KX4S selection inhibited) | ||||||
| * When using 4-20 mA input, attach 0.1 % of 250 Ω resistance to the input terminal of 1-5V d.c |
Specification
| Model | KX9N | KX7N | KX2N | KX3N | KX4N(S) | |||||||||
| Apperance |
|
|
|
|
| |||||||||
| W × H × D (mm) | 96 × 96 × 100 | 72 × 72 × 100 | 48 × 96 × 100 | 96 × 48 × 100 | 48 × 48 × 100 | |||||||||
| Function |
| |||||||||||||
| Power Voltage | 100 - 240 V a.c, 50 - 60 Hz (voltage fluctuation rate : ± 10 %) | |||||||||||||
| Power Consumption | Below 11 VA max | Below 7 VA max | ||||||||||||
| Input | Input type | Please refer to Input code | ||||||||||||
| Sampling cycle | 250 ms | |||||||||||||
| Indication accuracy | ±0.5 % (Please refer to Input type) | |||||||||||||
| Allowable voltage | ±20 V d.c for 1 minute | |||||||||||||
| Reference junction temperature | ±3.5 ?, 0 ~ 50 °C | |||||||||||||
| Operation after input break | Up scale after input break, output OFF | |||||||||||||
| Control Output | Relay | NO : 5 A 250 V a.c, 5 A 30 V d.c(Resistive load) NO : 3 A 250 V a.c, 1 A 30 V d.c(Resistive load) | ||||||||||||
| Voltage output | ON voltage : More than 12 V d.c min Load resistance: 600 Ω min | |||||||||||||
| Current output | Range : 4 - 20 mA d.c (±5%) Accuracy : ±0.2 mA Load resistance: 600 Ω max | |||||||||||||
| Retransmission output | Range : 4 - 20 mA d.c (±5 %) Accuracy : ±0.2 mA Load resistance: 600 Ω max | |||||||||||||
| Alarm output | 250 V a.c, 3 A (Resistive load) refer to connection diagram (contact) But, KX4N: 1a contact, 250 V a.c 1A (load resistance) | |||||||||||||
| Contact input | OFF resistance : 10 ㏀ min ON resistance : 1 ㏀ max | |||||||||||||
| Control | Method | PID control, ON/OFF | ||||||||||||
| Output operation | Reverse action, Direct action | |||||||||||||
| Anti-reset wind-up | Auto (A=0), 0.1 ~ 100.0 % | |||||||||||||
| Insulation Resistance | 20 ㏁ min between 1st and 2nd terminals | |||||||||||||
| Dielectric strength | 2,300 V a.c between 1st and 2nd terminals, for 1 minute | |||||||||||||
| Operating environment | Temperature & Humidity | 0 ~ 50 °C, 35 ~ 85 % R.H.( With no condensation) | ||||||||||||
| Environment | Please refer to safety information | |||||||||||||